User`s manual

10-38 Motion Mate DSM314 for Series 90-30 PLCs User's Manual
January 2001 GFK-1742A
10
Figure 10-40. Hardware Configuration 90-30 rack DSM314 CTL Bits Tab
This completes the configuration changes necessary for the example. Close the Hardware
Configuration tool and save the folder. To save the folder, select the File from the main menu and
then select Save All from the file menu.
The link between our example Local Logic program and the DSM314 module is now complete.
The user can now create any required PLC rung ladder logic and then perform a Check All on the
programs.
Downloading Your First Local Logic Program
To perform the download operation, we need to first make sure that the communications port is
properly configured. To access communications setup, select Tools from the main menu and then
select the Communications Setup sub menu. The menu selection invokes the communications
configuration package. The first dialog box will prompt the user for a password. The default (as
shipped) password is
netutil
(Figure 10-41).