User`s manual

Programmed Motion
GFK-1742A Chapter 7 Programmed Motion 7-43
7
If this program segment is not at the beginning of a program, and for some reason axis 2 has not
yet reached Block 20 when axis 1 has moved 30,000 counts, an error would occur. Axis 1 would
continue to 80,000 counts, and the DSM314 would report a Block Sync Error during a CMOVE
in the Status Code.
If it is imperative that the axes synchronize at Block 20, Changing Block 10 to a PMOVE would
guarantee synchronization, but then axis 1 would stop at 30,000 counts.