User`s manual
DSM to PLC Interface
GFK-1742A  Chapter 5 Motion Mate DSM314 to PLC Interface 5-23
5
time. For Analog mode, the “Vel at Max Cmd” configuration value must be set correctly for
proper operation of the 
Position Loop Time Constant
. A PLC reset or power cycle returns this
value to the configured data.
4.13 Velocity Feedforward.
 This command sets the 
Velocity Feedforward
 gain (0.01 percent).
It is the percentage of 
Commanded Velocity
 that is added to the DSM314 velocity command
output. Increasing 
Velocity Feedforward
 causes the servo to operate with faster response and
reduced position error. Optimum 
Velocity Feedforward
 values are 90-100 %. For analog servos,
the “Vel at Max Cmd” configuration value must be set correctly for proper operation of the
Velocity Feedforward
 gain factor. A PLC reset or power cycle returns this value to the
configured data.
4.14 Integrator Time Constant. 
(Milliseconds) This command sets the 
Integrator Time
Constant
 for the position error integrator. The value specifies the amount of time in which 63%
of the 
Position Error
 will be removed. The 
Integrator Time Constant
 should be 5 to 10 times
greater than the 
Position Loop Time Constant
 to prevent instability and oscillation.
 It is
recommended that the position error integrator only be used in continuous follower
applications. Use of the integrator in point to point positioning applications may result in
position overshoot when stopping.
4.15 Follower A/B Ratio. 
This command allows the PLC to update the slave 
:
 master A/B ratio
used in each follower loop. “A” is a 16-bit signed integer with a minimum value of -32,768 and a
maximum value of +32,767. “B” is a 16-bit integer with a minimum value of 1 and a maximum
value of 32,767. The magnitude of the A/B ratio must be in the range 32:1 to 1:10,000 or a status
error will be generated. Refer to Chapter 8 for additional information about the A/B ratio.
4.16 Velocity Loop Gain
. (VLGN
)
 Digital Mode only. The velocity control loop gain for a GE
Fanuc digital servo axis may be set with the 
Velocity Loop Gain
 command. The VLGN value is
used to match the load inertia (J
L
) to the motor inertia (J
M
). VLGN is defined with a default
value of 16 representing an inertia ratio of 1 to 1. The VLGN value is calculated assuming that
the load is rigidly applied to the motor. Therefore, in actual machine adjustment the required
value may significantly differ from the calculated value due to rigidity, friction, backlash, and
other factors. A PLC reset or power cycle returns VLGN to the value set in the configuration
software. A suggested starting point for 
Velocity Loop Gain
 is:
Load Inertia (J
L
)
Velocity Loop Gain =
Motor Inertia (J
M
)
x 16
The allowed range of 
Velocity Loop Gain
 is 0 to 255.
For example
: The motor inertia (J
M
) of a particular servo is 0.10 lb-in-s
2
. The load inertia (J
L
) in
this application is 0.05 lb-in-s
2
. VLGN = (0.05 / 0.10)
 * 
16 = 8
The default 
Velocity Loop Gain 
is set using the 
Velocity Loop Gain
 setting in the VersaPro
Configuration Software.
Caution
An incorrect VLGN value may cause an axis to be unstable. Care should be
used when making any change to the VLGN value.










