User`s manual

4-6 Motion Mate DSM314 for Series 90-30 PLCs User's Manual
January 2001 GFK-1742A
4
1.05
Total Encoder Power
. This parameter defines the total power consumption for all encoders
attached to the DSM module. (VersaPro Default =
0
). This parameter should account for all analog
axis and master encoders and is used to update the Power Consumption chart in VersaPro.
1.06
Motion Program Block Name
. This parameter defines the optional Motion Program block
name to execute on the DSM module. If no name is entered, the DSM will assume that Motion
Program blocks are not used. If a name is entered, a Motion Program block of the same name must
exist within the active folder. Entering an invalid name will cause an error to be generated when
storing the hardware configuration to the PLC. The name may consist of up to 31 characters, but
cannot have any blank spaces, although you are allowed to use the underline character. Both upper
and lower case characters are permitted. (VersaPro Default =
<blank>
).
1.07
Local Logic Block Name
. This parameter defines the optional Local Logic block name to
execute on the DSM module. If no name is entered, the DSM will assume that Local Logic blocks
are not used. If a name is entered, a Local Logic block of the same name must exist within the
active folder. Entering an invalid name will cause an error to be generated when storing the
hardware configuration to the PLC. The name may consist of up to 31 characters, but cannot have
any blank spaces, although you are allowed to use the underline character. Both upper and lower
case characters are permitted. For Local Logic to operate, the
Local Logic Mode
must also be set
to Enabled. (VersaPro Default =
<blank>
).
1.08
CAM Block Name
. Defines the optional CAM block name to execute on the DSM module. If
no name is entered, the DSM will assume that CAM blocks are not used. If a name is entered, a
CAM block of the same name must exist within the active folder. Entering an invalid name will
cause an error to be generated when storing the hardware configuration to the PLC. The rules for
CAM Block names are:
Only the characters A-Z, a-z, 0-9, and _ (underscore symbol) are allowed. Consecutive
underscores and blank spaces are not allowed.
The CAM block name must begin with a letter or underscore symbol.
A block cannot have the same name as another block that exists in an open folder.
A CAM block name may contain up to a maximum of seven characters.
This feature was first supported in DSM314 firmware release 2.00, and requires use of VersaPro
1.5 or later and the CAM Editor 1.0 or later; also CPU firmware 10.00 or later is required. See
Chapter 16 for CAM feature details.
(VersaPro Default =
<blank>
).
Serial Communications Port Configuration Data
The DSM314s Serial Communications Port uses an RJ-11 connector labeled COMM on the
module’s faceplate, and supports the RS-232 protocol. It is used for firmware upgrades to flash
memory and must be configured properly to communicate with the upgrade software running on
your programmer. Make sure the programmers configuration parameters and the DSM314’s
Serial Communications Port configuration parameters match. These configuration parameters are
described in Table 4-4.