User`s manual

3-42 Motion Mate DSM314 for Series 90-30 PLCs User's Manual
January 2001 GFK-1742A
3
24v DC Optically Isolated Output
Circuit
Identifier
Servo Axis 1-4 Circuit
Function
Aux 2-4 Axis
Circuit Function
Signal Name
(X = A, B, C, or
D Connector)
Faceplate
Pin
Auxiliary
Terminal
Board
Servo
Terminal
Board
OUT1 Faceplate 24v Output (+) Faceplate 24v Output (+) OUT1P_X 18 18 8
Faceplate 24v Output (-) Faceplate 24v Output (-) OUT1M_X 36 36 16
I/O Type:
24v DC Optically Isolated Output
Circuit Type:
Isolated Solid State Relay (SSR)
Output Current:
125 ma continuous, 500 ma for 10 ms (resistive or inductive)
Output Voltage Drop:
1.0 v max at 0.125 amps
Notes:
Output is protected by a 30v transzorb and a 0.2 amp Polyswitch. If
a short circuit occurs, the output will automatically switch to a high
impedance state until the load is removed. The load should not be
re-applied for 60 seconds. This is a dc output and it will appear to
be always ON if connections to it are reversed.
SOLID STATE
RELAY
OUT +
OUT -
30V