User`s manual
D:\manual\UM_PCM-ULT\ML_Ult3k\661-UT3K-002-31.doc
KEVIN KU 第 23 頁 2003/3/4
A
PPENDIX B
S
PECIFICATIONS
Tower model
700VA
1000VA
1500VA
2000VA
3000VA
19" rack-mount model
700VA RM
1000VA RM
1500VA RM
2000VA RM
3000VA RM
Power Rating
P.F.=0.7
700VA
490W
1KVA
700W
1.5KVA
1050W
2KVA
1400W
3KVA
2100W
Voltage
100V:76V-130V 110V:80V-138V 115V:83.5V-140V
120V:87V-140V
208V:152V-260V 220V:160V-276V 230V:167V-280V
240V:174V-280V
Frequency
50Hz or 60Hz
±
3Hz
Phase Single phase
AC Input
Power factor 0.98
Dc voltage
24V
36V
48V
72V
96V
Back-up Time Full Load
5min
7min
5min
9min
7min
Half Load
12min
20min
17min
20min
15min
Type
Sealed lead acid battery, free maintenance
Protection
Cut off without draining any current when battery low
Battery
Recharge time
About 8 hours to 90% after fully discharged
Frequency 50Hz/60Hz (Auto detection)
Voltage 100/110/115/120V or 208/220/230/240V
Voltage regulation
±
2% (except 3000VA/110V
±
3%, 3000VA RM/110V
±
3%
Frequency stability
±
0.5%
Power factor 0.7 (lagging)
Harmonic distortion <3% of T.H.D. at linear load
Overload detection 105% for 10 seconds and 130%
±
10% for 300ms
AC output
Crest factor ratio 3:1
Efficiency
AC to AC >85%
Power failure or
recovery
0ms Transfer
Overload disappear Auto transfer to UPS
Noise Level
1m. distance <45dBA <52dBA
Status line input (green), inverter output (green), bypass (yellow), fault
(red)
Battery capacity 4 green, 1 red LED and red bar LEDs indicated low capacity
LED
Indicators
Load level 4 green, 1 red LED and red bar LEDs indicated overload
capacity
Battery discharge The first warning will beep every 4 seconds to indicate battery in
use.
The second warning will beep every 1 second to signal battery
low condition.
Alarm
UPS fault Continuous beeping sound
19