Installation manual

13
4. Make the UPS terminal strip connections and all other AC wiring connections.
Refer to the proper installation wiring diagram for your application (see Table 9, page 10).
Read the notes below the wiring diagram carefully.
See Figure 9 for proper UPS output terminations.
Make all terminal strip connections as shown on the proper wiring diagrams.
Good grounding (earth) connections are necessary to reduce electrical noise and for safe
operation of the UPS and loads. Follow the grounding guidelines on the installation wiring
diagram.
The loads must be balanced on the UPS output.See Table 11 on page 25, for maximum
output current per phase (leg).