Specifications
The Answer in Power Protection
SOLA 610 UPS Optional Maintenance and Warranty
Input
Input Voltage Range: 240 Volts +10%, -20%
Input Frequency Range: 50/60 Hz + 5% (Auto Selecting)
Input Current (Nom. Full Load): 700VA = 2.9A
1000VA = 3.8A
1500VA = 5.5A
2000VA = 7.4A
3000VA = 11.4A
Line Cord: Australian Plug to IEC Connector (10 A)
For 3kVA - 15 A plug and connector
Output
Output Voltage: 240 Volts + 3% Linear Load (208, 220,
230 V optional - set by rear panel dip
switches)
Output Frequency: Automatic. Conforms to Input (50 or 60
Hz)
Output Frequency Regulation: + 0.5% Inverter free running
(Phase locked to input under normal
conditions)
Distortion: Less than 4% full linear load
Overload Capacity: > 130% for 1.5 seconds
Output Sockets: 10 Amp Australian Sockets
Efficiency
AC to AC Efficiency: 80% minimum (full load @ 0.7 pf, fully
charged batteries)
Battery
Type: Sealed Maintenance Free
DC Voltage: See Internal Battery Data Table (page 31)
Runtime: See Internal Battery Data Table (page 31)
Bypass
UPS to/from Bypass Transfer Time: Less than 4 milliseconds (2.5 msec
Typical)
Auto-reverse: Returns to normal mode after overload
condition removed.
Acoustic Noise
Audible noise at 1 metre: 45-50 dBA (model dependent)
Environmental
Operating Temperature: 0
o
C to 40
o
C altitude < 1500 m
10
o
C to 35
o
C altitude 1500 - 3000 m
(NOTE: High temperature decreases
Battery life)
Storage Temperature: -15
o
C to +45
o
C
Humidity: 20-90% non-condensing
5.4 Model Specifications
“A” Model (Australian Version)
16