Specifications
The Answer in Power Protection
SOLA 610 UPS Optional Features
4.3 Installing and Operating CheckUPS II®
You may wish to have additional output alarms or interface with
an IBM AS400® unit. In this situation, you will need to purchase
an additional alarm card option (Part No. 0610-AS400) which
will install in the communications slot on the rear of the UPS.
The AS400® card option is fitted with two (2) connectors, one
DB9 female and one ES 2 pin. The output available from these
connectors is as follows:-
Output 1 (DB9 female connector)
4.4 Installation and Operation of the AS400® card option
Pin. No. Signal Name Definition I/O Comments
1 UPS Fail Normally open, Active will close O Relay contact
2 Summary Alarm Normally open, Active will close.
Active when UPS fails, bypass
activated, Utility input failure and
low battery status
O Relay contact
3 Remote Shutdown (-) Ground
4 Remote Shutdown (+) Activated by +5~12V for 1 sec
duration
I
5 Common Common connection for Pins
1,2,6,7,8 & 9
Relay common
6 Bypass Normally open. Will close when
UPS is in Bypass Mode.
O Relay contact
7 Battery low Normally open. Will close when
battery is almost fully discharged.
O Relay contact
8 UPS - ON Normally open. Will close when
UPS is on.
O Relay contact
9 Utility Line Failure Normally open. Will close when the
AC input fails.
O Relay contact
11
Your UPS is supplied with a CD-ROM and
communications cable to install and operate CheckUPS
II®.
To install CheckUPS II
®
on your computer, follow the
installation enclosed with the CD-ROM.