SECTION 4 • INSTALLATION
GENERAL
The DVR
®
2000E is delivered in a sturdy carton to prevent shipping damage. Upon receipt, check the part number
against the requisition and packaging list for agreement. Inspect for damage, and if there is evidence of such,
immediately le a claim with the carrier and notify your sales representative or a sales representative at Marathon
Electric.
If the unit is not installed immediately, store it in the original shipping package in a moisture and dust free
environment.
MOUNTING
The DVR
®
2000E is normally located in the generator conduit box. It is designed for behind the panel mounting
and requires a cutout for front panel viewing and access. Mounting hardware consists of six customer supplied,
#12 thread-forming screws that pass through mounting holes in the conduit box and thread into the plastic shell
of the DVR
®
2000E. The unit must be mounted where the ambient temperature does not exceed the allowable
environmental conditions called out in Section 1, General Information, Specifi cations. DVR
®
2000E package
dimensions are shown in Figure 4-1. Cutout and drilling dimensions are shown in Figure 4-2.
When the DVR
®
2000E Voltage regulator is mounted on the generator at the factory a molded cover is provided.
This cover allows the system to be in compliance with UL 508 as live terminals and heatsinks could be exposed
to unintentional contact. As stated this cover must be installed whenever the voltage regulator is energized.