Technical Specifications

ILLUMINATION
Works with or without an AC ballast to convert new or exist-
ing fluorescent fixtures in to unobtrusive emergency lighting.
Operates one lamp in the emergency mode for a minimum
of 90-minutes.
Provides a maximum initial lumen output of 500 lumens.
ELECTRICAL
Dual 120/277 voltage.
Charge rate/power “ON” LED indicator light and push-to-test
switch for mandated code compliance testing.
2.4V long-life, maintenance-free, rechargeable sealed NiCd
battery.
Internal solid-state transfer switch automatically connects
the internal battery to fluorescent lamp for minimum
90-minute emergency illumination.
Fully automatic solid-state, two rate charger initiates battery
charging to recharge a discharged battery in 24 hours.
MOUNTING
Suitable for installation inside, on top or in remote* of the
fixture.
Can be used in both switched and unswitched fixtures.
UL Listed for factory or field installation.
HOUSING
Durable painted steel construction in white finish.
Compact design fits most fluorescent fixtures.
WARRANTY / LISTING
Five year warranty against defects in material and workman-
ship (lamps excluded).
Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,
Local and State Codes.
UL Listed for damp locations (0°C – 50°C).
LAMP COMPATIBILITY
Compatible with most one-, two-, three-, and four-lamp
electronic, standard and dimming AC ballasts.
Operates one 17W-40W T8 through T12, one 13W-26W
4-pin compact, one 18W-36W 4-pin long compact fluores-
cent lamps. Refer to lamp compatibility chart for a complete
list of lamps.
DIMENSIONS
* When battery packs are remote mount-
ed, the remote distance cannot exceed ½
of the distance from ballast to lamp speci-
fied by the A.C. ballast manufacturer. The
maximum allowable remote mounting
distance is 50 feet.
LED Test
switch included.