Installation Manual

11
/ Installation requirements / Electrical connection
FOUR-WIRE CONN.RECEPTACLE NEMA 14-50R
THREE-WIRE CONN.RECEPTACLE NEMA 14-50R
Check your local code for which of the options be-
low  should be used  in grounding the receptacle 
power supply connections.
OPTION 1 – FOUR Wires connection: 
-Connect the L1 receptacle terminal to the inco-
ming BLACK electrical supply wire (L1-hot wire)
-Connect the L2 receptacle terminal to the inco-
ming RED electrical supply wire (L2-hot wire)
-Connect  the  NEUTRAL  receptacle  terminal  to 
the incoming  NEUTRAL (WHITE)  electrical  sup-
ply wire
-Connect the GROUND receptacle terminal to the 
incoming  GROUND  (GREEN)  electrical  supply 
wire
OPTION 2 - THREE-Wires connection: 
-Connect the L1 receptacle terminal to the inco-
ming BLACK electrical supply wire (L1-hot wire)
-Connect the L2 receptacle terminal to the inco-
ming RED electrical supply wire (L2-hot wire)
-Connect the NEUTRAL with the GROUND recep-
tacle terminal to the incoming NEUTRAL (WHITE) 
electrical supply wire
DO  NOT  USE  EXTENSION  CORDS  WITH 
THIS APPLIANCE AS IT MAY RESULT IN FIRE, 
ELECTRIC SHOCK OR OTHER type of PERSO-
NAL INJURY.
The  appliance  is  equipped  at  the  factory  with 
an electric supply cord set 4 wires type with ring 
terminals (L1,  L2, N,  Ground) suitable  for range 
use UL/CSA listed type SRDT/DRT 2x6AWG (L1, 
L2)+2x8AWG (N, G) rated 300V, 40 or 50A with 
fused plug type NEMA 14-50P; cable length 1,5 
m.; in case the supply cord set must be replaced, 
it shall be replaced with an identical set having the 
same technical specs and following carefully the  
instructions and diagrams below: