Installation Manual for Dual Fuel Ranges EN
10
/ Installation requirements / Electrical connection
ELECTRICAL
A properly-grounded horizontally- mounted electri-
cal receptacle should be installed no higher than 
3” (7.6 cm) above the fl oor, no less than 2” (5 cm) 
and no more than 8” (20,3 cm) from the left side 
(facing product). 
Check all local code requirements.
GAS
An  agency-approved,  properly-sized  manual 
shut-off  valve should be installed no higher than 
3” (7.6 cm) above the fl oor and no less than 2” (5 
cm) and no more than 8” (20.3 cm) from the right 
side (facing product). 
To connect gas between shut-off valve and regula-
tor, use agency-approved, properly sized fl exible 
or rigid pipe. Check all local code requirements.
Warning! 
ELECTRICAL SHOCK HAZARD
Disconnect electrical power at the circuit bre-
aker box or fuse box before installing the ap-
pliance.
Provide appropriate ground for the appliance.
Use copper conductors only.
Failure to  follow  these instructions  could  re-
sult in serious injury or death.
Warning! 
Electrical grounding
This  appliance  is  equipped  with  a  three-prong 
plug for your protection against shock hazard and 
should be plugged directly into a properly groun-
ded socket. Do not cut or remove the grounding 
prong from this plug.
Caution
Label  all  wires  prior  to  disconnecting  when 
servicing  controls.  Wiring  errors  can  cause 
improper and dangerous operation.
Verify proper operation after servicing.
The appliance shall be connected to a single pha-
se electric line rated at 120/208Vac or 120/240Vac 
and 60Hz frequency.
Install a suitable electric power supply receptacle 
connection type NEMA 14-50R able to support a 
load of at least 30 A (per line) according to local 
code requirements. For four or three wires power 
supply connection system see diagram below.
INSTALLATION REQUIREMENTS ELECTRICAL CONNECTION
installation area for the connection
Type Voltage Circuit rating Electrical 
supply
30” DFM 120/208V
120/240V
2900W 14A
3700W 16A
20A
20A
30” DFS 120/208V
120/240V
4300W 21A
5600W 24A
30A
30A
36” DFM 120/208V
120/240V
2900W 14A
3700W 16A
20A
20A
36” DFS 120/208V
120/240V
4500W 22,5A
5900W 25,5A
30A
30A
48” DFM 120/208V
120/240V
5400W 30A
6700W 33A
40A
40A
48” DFS 120/208V
120/240V
6800W 36,5A
8500W 40,5A
40A
40A