GFR Thermostat Installation Manual
OPERATION CHECK
1. After your G Series wall heater has been completely
installed, all thermostats, whether single pole or double pole,
should be turned to LOW or OFF. Turn on breakers or
install fuses. Wait 3 to 5 minutes and check to make sure the
heater is not operating. Should it be operating, disconnect
power and check your wiring. If not operating, turn the
thermostat to the highest position and wait another 3 to 5
minutes. Then check to see that all heaters are operating.
Should it not be operating, again disconnect power and
check your wiring.
2. Allow heater to operate steadily for 1/2 hour.
3. Select the setting for your comfort level.
NOTE: Your electric heating system has many advantages,
one of which is zone or room-by-room control. If you desire to
keep a seldom used room at a lower temperature, this may be
done by lowering the thermostat setting and closing the door.
However, DO NOT try to control different rooms at different tem-
peratures unless the doors are kept closed. This will tend to
increase operating cost and decrease comfort. It is advisable,
if rooms are kept open, that all thermostats have the same set-
ting. By following these instructions you will enjoy greater com-
fort.
LIMITED WARRANTY
All products covered by this instruction sheet are warranted against defects in workmanship and materials for one year from date of installation. This warranty does not apply
to damage from accident, misuse, or alteration; nor where the connected voltage is more than 5% above the nameplate voltage; nor to equipment improperly installed or wired
or maintained in violation of this instruction sheet. All claims for warranty work must be accompanied by proof of the date of installation.
The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor costs, and shipping costs incurred to return products to a
Marley Engineered Products Service Center, and we will repair or replace, at our option, at no charge to you with return freight paid by Marley. It is agreed that such repair
or replacement is the exclusive remedy available from Marley Engineered Products.
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS
AGREEMENT. MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT,
WHETHER BASED UPON NEGLIGENCE, TORT, STRICT LIABILITY, OR CONTRACT.
Some states do not allow the exclusion on limitation of incidental or consequential damages, so the above exclusion or limitation may not apply to you. This warranty gives
you specific legal rights, and you may also have other rights which vary from state.
For the address of your nearest authorized service center, contact Marley Engineered Products, 470 Beauty Spot Road East, Bennettsville, SC 29512 USA. Merchandise
returned to the factory must be accompanied by a return authorization and service identification tag, both available from the above location. When requesting return autho-
rization, include all catalog numbers shown on the products.
5200-2426-001
10/08
ECR 37958
2
FIELD WIRE & PROTECTION CHART
TABLE 2
TOTAL AMPS
0 thru 12
12.1 thru 16
16.1 thru 24
WIRE SIZE
(COPPER)
#14
#12
#10
CIRCUIT BREAKER
OR FUSE SIZE
15 Amps
20 Amps
30 Amps
IMPORTANT INFORMATION
NAMEPLATE
DATE CODE
0399 GTSP
Marley Engineered Products1 POLE STAT
BENNETTSVILLE, SC 29512 774G LISTED
ROOM HEATER
ACCESSORY
4104-2160-004 VAC 60 HZ AMPS
120 - 240 22 RES.
470 Beauty Spot Rd. East
Bennettsville, SC 29512 USA
HOW TO OBTAIN WARRANTY SERVICE AND
WARRANTY PARTS PLUS GENERAL INFORMATION
1. Warranty Service or Parts 1-800-642-4328
2. Purchase Replacement Parts 1-800-654-3545
3. General Product Information www.marleymep.com
Note: When obtaining service always have the following:
1. Model number of the product
2. Date of manufacture
3. Part number or description