Switching off the lighting
- if no more motion is detected after a set delay time
- when the brightness setpoint is exceeded by more than 100 % for
approx. 15 min.
Detection
■
Detection of motion from above (ceiling mounting)
■
Circular detection field with a diameter of 8 m (on the floor when
mounted at the nominal mounting height)
■
Detection of even the smallest motions (writing or working with a
mouse/keyboard) thanks to dense arrangement of the sensor fields
in the core area of the detection field (see illustration below)
Recommendation: installation directly over the work area
■
Cover plate for limiting the detection area and masking out sources
of interference include in scope of delivery (see illustration below)
■
Walk test mode for testing the detection area can be activated via
button
■
Master/slave operation of several presence sensors possible for
monitoring larger areas
Settings
■
Brightness setpoint value, delay time and detection sensitivity can
be set via potentiometer on the device
■
Adjustment of the brightness setpoint via taught-in radio transmitter
PRESENCE DETECTORS
Function
■
Lighting control e. g. at work area by
- monitoring of the detection area with PIR sensor
- Detection of the ambient brightness for lighting control
■
Energy savings from needs-related lighting control, i. e. when people
are present and the ambient brightness is not sufficient
System integration
■
Lighting control with all radio bus dimming/switch actuators from release
2 (R2) onwards
Lighting control with dim actuator
■
Implementation of constant light control: Control of the dimming value
taking into account the ambient brightness, so that the actual bright-
ness value measured at the presence detector always corresponds to
the saved setpoint
■
Switching off the lighting
- if no more motion is detected after a set delay time
- when the brightness setpoint is exceeded by 40 %
Lighting control with switch actuator
■
Lighting control in 2-point operation, including switching on of the
lighting when the brightness actual value at the radio presence
detector is less than the brightness setpoint
Technical data
Supply voltage: 6 V =
Battery: 4 x 1.5 V Micro alkaline
Battery service life: approx. 3 years
Battery empty indication: 10 x flashing of the LED after
Sensor window when transmitting
Detection angle: 360°
Nominal mounting height: approx 2.50 m
Size of the detection area: Ø approx. 8 m
Size of the detection area at desk height: Ø approx. 5 m
Switch-on time: adjustable from approx.
260 min.
Sensitivity: adjustable from 20100 %
Brightness setpoint for lighting control: approx. 32000 lux
Operating temperature: 0 to 45 °C
Protection class: IP 20
Dimensions: Ø = 103 mm
Height = 42 mm
Order no.: 0182 09
Side view with setting
potentiometers
Segment division
Detection area
0 m 4 m2 m
4 m
approx.
2.5 m
approx.
2.5 m
sens time lux