9. Trouble-Shooting Problems
The following guide can be used to pinpoint the cause of operational problems with the BWC XL.1 wind
turbine and the PowerCenter controller. For problems or symptoms not found in the following listing,
please contact the Service Department at Bergey Windpower Co. at:
Tel: 405-364-4212
Fax: 405 364-2078
e-mail: pieter@bergey.com
PROBLEM
CAUSE(S)
DIAGNOSIS
REMEDY
Battery voltage gets
too high.
PowerCenter regulating
voltage set too high
Excessive battery gass-
ing. Use voltmeter to
check battery cell vol-
tages or hydrometer to
check the specific gravi-
ty compare to battery
manufacturers recom-
mendations.
Adjust battery regulation
voltage as on page 9
During operation without
dump load, battery vol-
tage can vary up to 1
volts above reg. voltage
for a few seconds when
in Slow Mode
Use multi-meter to indi-
cate battery voltage
Normal operation, OK
for flooded lead acid
batteries. For sealed
batteries recommend
adjusting the set voltage
lower, or use a dump
load which will allow
very precise regulation
Batteries do not reach
full state of charge.
PowerCenter regulating
voltage set too low.
Use hydrometer to
check the specific gravi-
ty of the battery cells.
Compare with battery
manufacturer’s recom-
mendation.
Adjust battery regulation
voltage as on page 9
Loads are too large.
Remove largest load. If
battery bank reaches
higher state of charge,
then the system is over-
loaded.
Consult with BWC about
possible remedies.