Owners manual
Motorised Battery Switch 
Model: 720-MDVSO 12/24V Voltage Sensitive Switch
OPERATION AND INSTALLATION INSTRUCTIONS
SPECIFICATIONS:
• Continuous rating:  500 Amps DC -minimum 2x95mm² (2x 3/0) cables
• Intermittent rating:  700 Amps DC -minimum 2x95mm² (2x 3/0) cables
• Cranking rating:  2500 Amps DC -minimum 2x95mm² (2x 3/0) cables
• Maximum Voltage:  32 Volts DC (12V or 24V systems)
• Voltage Note:  Both battery banks must be the same voltage, either 12V or 24V
• Operating Voltage:  8 to 30.5 Volts DC
• VSS Engages:  13.3V (26.6V)
• VSS Disengages:  12.7V (25.4V)
• Sensing:  Senses voltage on both battery banks
• Operation:  Manual On/Off, Auto On/Off
• Mounting:  Recessed or surface
• Ignition protected  Meets UL 1107 standards
• IP Rating  IP65
• Stud Size:  2 x 12mm (1/2”) –See Installation section for torques
• Materials:  Tinned copper conductors/studs, stainless steel nuts,
  high temperature bre reinforced plastics
• Power draw:  Off/Auto Off: 5mA @12V, 5.5mA @24V
Auto On/On:  8.3mA @12V, 12.5mA @24V
• Emergency Parallel:  Remote switch activates parallel for 10 minute period
  Pressing remote switch for 6 seconds, deactivates
  parallel function.
Remote  emergency  parallel  VSS  control  is  achieved  by  using  a  remotely 
mounted momentary switch, such as the BEP #80-724-0007-00 unit (pictured 
at right), which also features an LED to show the VSS status. When operated, 
the remote switch engages the 720-MDVSO contacts, paralleling the batteries, 
for a 10 minute period, for example to get an engine started following a at start 
battery. 
Alternatively, the VSS can be manually overridden to either “Manual On”, 
or “Manual Off” modes.