User's Guide

Modbus Settings
The Ranger Pro sensors publish vibration and temperature (process variable data) values as 32-
bit, floating point data. You can output Ranger Pro static data like vibration and temperature
using the gateway's Modbus interface.
To modify Modbus settings in the gateway, refer to the vendor's documentation.
Phase 1 Ranger Pro Devices
Devices use firmware version 01.01.06.03 or earlier.
Byte Order: Little Endian, 32-bit
Data type: float
l CH01_AI: Tagname.CH01_AI.PV = Temperature
l CH02_AI: Tagname.CH02_AI.PV = X-Accel
l CH03_AI: Tagname.CH03_AI.PV = X-Vel
l CH04_AI: Tagname.CH04_AI.PV = Y-Accel
l CH05_AI: Tagname.CH05_AI.PV = Y-Vel
l CH06_AI: Tagname.CH06_AI.PV = Z-Accel
l CH07_AI: Tagname.CH07_AI.PV = Z-Vel
Phase 2 Ranger Pro Devices
For details about configuring single, tri-axial and repeater AIO objects for ISA100 devices,
refer to DD or CFfile release notes.
Devices use firmware version 02.01.02.02 or later.
Byte Order: Little Endian, 32-bit
Data type: float
l CH01_AI: Tagname.Temperature.PV
l CH02_AI: Tagname.Z-Axis-Accel.PV
l CH03_AI: Tagname.Z-Axis-Vel.PV
l CH04_AI: Tagname.Z-Axis-PkDemod.PV
l CH05_AI: Tagname.Y-Axis-Accel.PV
l CH06_AI: Tagname.Y-Axis-Vel.PV
l CH07_AI: Tagname.X-Axis-Accel.PV
l CH08_AI: Tagname.X-Axis-Vel.PV
Phase 3 Ranger Pro WirelessHART Devices
Use these device variable IDs to map WirelessHART Ranger Pro device variables to Modbus
registers.