Technical data
Natural Gas (G20 I
2H
) Tubular Heater
The minimum allowable pre-purge time requires calculating [BS EN1020:1998 clause 6.38].
To do this only the Carbon Dioxide CO
2
figure needs to be measured.
E.G. on a model 170 the calculated minimum time is = 354.8 / ((100 / CO2) + 1)
If the measured CO
2
is 6.7%
Then 100 / 6.7 = 14.9
14.9 + 1 = 15.9
Therefore minimum pre-purge time is = 354.8 / 15.9 = 22.3 seconds
The calculation to be conducted is given below for all models:
Model 40 Minimum pre-purge time = 628.8 / ((100 / CO2) + 1)
Model 70 Minimum pre-purge time = 475.4 / ((100 / CO2) + 1)
Model 100 Minimum pre-purge time = 398.0 / ((100 / CO2) + 1)
Model 135 Minimum pre-purge time = 366.8 / ((100 / CO2) + 1)
Model 170 Minimum pre-purge time = 354.8 / ((100 / CO2) + 1)
Model 200 Minimum pre-purge time = 347.4 / ((100 / CO2) + 1)
Model 250 Minimum pre-purge time = 286.2 / ((100 / CO2) + 1)
Model 330 Minimum pre-purge time = 269.7 / ((100 / CO2) + 1)
Model 410 Minimum pre-purge time = 261.4 / ((100 / CO2) + 1)
Model 490 Minimum pre-purge time = 269.2 / ((100 / CO2) + 1)
The pre-purge time must then be measured. If the measured pre-purge time is lower
than the calculated time STOP and contact Benson Heating.