Technical information
26
Ø100
MAX 500
*
L1
MIN. 400
C
12
: Horizontal flue installation twin pipe and concentric flue terminals.
✴
100 mm type 1 – 2 – 3
150 mm type 4 – 5 – 6
INSTALLATION DISTANCES FOR FLUE PIPE:
TYPE UNIT
TWIN PIPE SYSTEW HORIZONTAL CONCENTRIC TERMINAL
L1 MIN. L1 MAX. L2 MIN. L2 MAX.
1
m 1,00 2,50 1,50 2,50
2
m 1,00 2,50 1,50 2,50
3
m 1,00 2,50 1,50 2,50
4
m 1,00 2,50 1,50 2,50
5
m 1,00 2,50 1,50 2,50
6
m 1,00 2,50 1,50 2,50
• Only manufacturers recommended flue must be used
• When designing the flue consideration should be made for entrapment and disposal of any condensate
• Each bend corresponds to between 0,8-1 meter of horizontal pipework
• The flue installation must comply with all the relevant regulations regarding height and position from all openings
MIN. 400
L2
MAX 300
*
Ø100
Ø150