Technical information

25
L1
MAX 500
Ø100
MIN. 400
B
22
: Single pipe flue to outside wall or roof terminal. Combustion air from inside
building
INSTALLATION DISTANCES FOR FLUE PIPE:
TYPE UNIT
HORIZONTAL FLUE
V
ERTICAL FLUE
L1 MIN. L1 MAX. L2 MIN. L2 MAX.
1
m 1,00 5,00 1,00 10,00
2
m 1,00 5,00 1,00 10,00
3
m 1,00 5,00 1,00 10,00
4
m 1,00 5,00 1,00 10,00
5
m 1,00 5,00 1,00 10,00
6
m 1,00 5,00 1,00 10,00
Only manufacturers recommended flue must be used
When designing the flue consideration should be made for entrapment and disposal of any condensate
Each bend corresponds to between 0,8-1 meter of horizontal pipework
The flue installation must comply with all the relevant regulations regarding height and position from all openings.
Ø100
MIN 400
L2