User manual
3.9.6 SW1 DIP Switch
The DIP switch on the card changes the analog input and analog output between 0-10V or 0-20mA. The picture below shows how to adjust
the switch to select the desired signal. Switching to the up or top position is ON and switching towards card or down is OFF.
Remote LCD Keypad/Display
3.10 Remote LCD Keypad/Display
The display has a NEMA 13/IP65 service rating. The display is available in 2 versions, a small display as P/N KPMX3SLCD and large
display as P/N KPMX3LLCD.
3.10.1 Remote Display
The MX
2
control has one of two types of keypads, either a LED display or a LCD display. As standard, a LED display is permanently
mounted on the control board. The LCD keypad is optional and is mounted remotely from the MX
2
Control card via a straight through
CAT5 ethernet cable which connects between the MX
2
RJ45 terminal and remote display's RJ45 terminal.
43
3 - INSTALLATION
ANALOG OUTPUT
SW1-2
ON = 0-10V
OFF = 0-20mA
ANALOG INPUT
SW1-1
ON = 0-20mA
OFF = 0-10V
Figure 18: DIP Switch Settings