2.3.4 Inside Delta Connected Standard Duty (350% for 30 sec) Ratings
z NOTE: Do not exceed Class 10 overload setting.
17
2 - TECHNICAL SPECIFICATIONS
INSIDE DELTA Std Duty (350% start for 30 seconds 115% Continuous)
MODEL NUMBER
NOMINAL
AMPS
HORSEPOWER RATING
200-208V 220-240V 380-415V 440-480V 575-600V
RB2-1-S-125A-14C 180 60 75 100 150 200
RB2-1-S-156A-14C 240 75 100 150 200 250
RB2-1-S-180A-14C 279 75 100 150 200 250
RB2-1-S-180A-15C 279 75 100 150 200 250
RB2-1-S-240A-15C 361 125 150 200 300 400
RB2-1-S-302A-15C 414 150 150 250 350 400
RB2-1-S-361A-16C 515 200 150 250 450 400
RB2-1-S-414A-17C 590 200 250 350 500 600
RB2-1-S-477A-17C 720 250 300 400 600 700
RB2-1-S-515A-17C 800 250 300 500 600 700
RB2-1-S-590A-18C 838 300 350 500 700 800
RB2-1-S-720A-19C 1116 300 350 700 900 800
RB2-1-S-838A-20C 1300 400 500 800 1000 1200
Table 7: Inside Delta Standard Duty Horsepower Ratings