APPENDIX E - MODBUS REGISTER MAP
Absolute Register Address Description Range Units
30184/40184 Inline Enable
0: Disabled
1: Enabled
-
30185/40185 Inline Delay Time 10 – 100 100 mSec
30186/40186 Bypass Feedback Time 1 – 50 100 mSec
30187/40187 Keypad Stop
0: Disabled
1: Enabled
-
30188/40188 Modbus Timeout Enable
0: Disabled
1: Enabled
-
30189/40189 Modbus Timeout 1 – 120 Sec
30190/40190 CT Ratio (x:1)
0: 72:1
1: 96:1
2: 144:1
3: 288:1
4: 864:1
5: 2640:1
6: 3900:1
7 5760:1
8: 8000:1
9: 14400:1
10: 28800:1
-
30191/40191 Auto Start
0: Disabled
1: Start after power applied
2: Start after fault reset
3: Start after power applied and after
fault reset
-
30192/40192 Energy Saver Enable
0: Disabled
1: Enabled
-
30193/40193 Heater / Anti-Windmill Enable
0: Disabled
1: Enabled
-
30194/40194 Heater / Anti-Windmill Level 1 – 25 % FLA
30195/40195 Starter Type
0: Normal (Outside Delta)
1: Inside Delta
2: Wye-Delta
3: Phase Controller
4: Current Follower
5: Across the Line (Full Voltage)
-
30196/40196 LED Display Meter
0: Status
1: Ave Current
2: L1 Current
3: L2 Current
4: L3 Current
5: Current Imbalance %
6: Residual Ground Fault
7: Ave. Volts
8: L1-L2 Volts
9: L2-L3 Volts
10: L3-L1 Volts
11: Overload
12: Power Factor
13: Watts
14: VA
15: vars
16: kW hours
17: MW hours
18: Phase Order
19: Line Frequency
20: Analog Input
21: Analog Output
22: Running Days
23: Running Hours
24: Starts
25: TruTorque %
26: Power %
27: Peak Starting Current
28: Last Starting Duration
-