2.2.5 CT Ratios
z NOTE: See P78/FUN 03 (CT Ratio) parameter on page 126 for more information.
Starter Power Ratings
2.3 Starter Power Ratings
Each RB2 model starter is rated for three different starting duties. For example, a starter can operate a:
300HP motor for a standard duty start (350% for 30 seconds)
Or
200HP for a heavy duty start (500% for 30 seconds)
Or
150HP motor for a severe duty start (600% for 30 seconds)
Or
450HP motor when connected to the inside delta of a motor for a standard duty start (350% for 30 seconds)
13
2 - TECHNICAL SPECIFICATIONS
CT Ratio
Minimum FLA
(A rms)
Maximum FLA
(A rms)
72:1
(4 wraps 288:1)
4
16
96:1
(3 wraps 288:1)
5 21
144:1
(2 wraps 288:1)
8 32
288:1 15 64
864:1 45 190
2640:1 135 590
3900:1 200 870
5760:1 295 1285
8000:1 410 1800
14400:1
(CT-CT combination)
740 3200
28800:1
(CT-CT combination)
1475 6400
Table 3: CT Ratios