User manual

Single Phase Soft Starter
7.10 Single Phase Soft Starter
There are times a single phase motor may need to be started using a soft starter. This can be accomplished with any 3 phase starter with
the following modifications to the starter.
Connect Line power to terminals L1 and L3.
Remove gate leads from J8 and J9 and tie off so the leads will not touch anything
Remove gate leads from J6 and reinstall to J8, from J7 and reinstall to J9
Change Input Phase Sensitivity, (P77/FUN 04) to “SPH” Single Phase.
Connect motor to terminals T1 and T3.
164
7 - THEORY OF OPERATION
START
Starters
stop
reset
enter
menu
MX2 CARD
BIPC-300055-01
Figure 44: Power Schematic for RB2 Integral Bypass Power Stack for Single Phase Operation