User manual
112
6 - PARAMETER DESCRIPTION
P52, 53, 54 Relay Output Configuration I/O 05, 06, 07
LED Display LCD Display
Range
LED LCD Description
OFF Off Off, Not Assigned. May be controlled over Modbus (Default R2 & R3)
FLFS Fault FS Faulted – Fail Safe operation. Energized when no faults present,
de-energized when faulted. (Default R1)
FLnF Fault NFS Faulted– Non Fail Safe operation. Energized when faulted.
run Running Running, starter running, voltage applied to motor.
utS UTS Up to Speed, motor up to speed or transition to for Wye/Delta
Operation.
AL Alarm Alarm, any alarm condition present.
rdYr Ready Ready, starter ready for start command.
LOC Locked Out Locked Out.
OC Overcurrent Overcurrent Alarm, overcurrent condition detected.
UC Undercurrent Undercurrent Alarm, undercurrent condition detected.
OLA OL Alarm Overload Alarm.
ShFS Shunt FS Shunt Trip Relay – Fail Safe operation, energized when no shunt trip.
fault present, de-energized on shunt trip fault.
ShnF Shunt NFS Shunt Trip Relay – Non Fail Safe operation, de-energized when no
shunt trip fault present, energized on shunt trip fault.
g
FLt Ground Fault A Ground Fault trip has occurred.
ES Energy Saver Operating in Energy Saver Mode.
HEAt Heating Motor Heating, starter applying heating pulses to motor.
SSPd Slow Spd Starter operating in slow speed mode.
SS F Slow Spd Fwd Starter operating in slow speed forward mode.
SS r Slow Spd Rev Starter operating in slow speed reverse mode.
dcb Braking Starter is applying DC brake current to motor.
FAn Cool Fan Ctl Heatsink fan control.
Description I/O parameters 1 - 3 configure which functions are performed by the R1 to R3 relays.
See Also Up To Speed Time (P9 / QST 09) parameter on page 82.
Over Current Level (P32 / PFN 01) parameter on page 98.
Under Current Level (P34 / PFN 03) parameter on page 100.
Residual Ground Fault Level (P37 / PFN 06) parameter on page 102.
Inline Configuration (P63 / I/O 16) parameter on page 118.
Heater Level (P73 / FUN 08) parameter on page 123.
Energy Saver (P72 / FUN 09) parameter on page 122.
Theory of Operation section 7.1.3, Motor Overload Operation on page 134.
Theory of Operation section 7.8, Wye-Delta Operation on page 160.
Theory of Operation section 7.9, Across The Line (Full Voltage Starter) on page 163.
Appendix B - Fault Codes on page 196.
I/O: R3 Config
07 Off
I/O: R2 Config
06 Off
I/O: R1 Config
05 Fault FS
P53
P54
P52