User manual
88
DC Inj Time  FUN 08 
DC Inj Level  FUN 09 
FUN: DC Inj Time
08   0.2 sec 
FUN: DC Inj Lvl
09  50.0%  
7 - PARAMETER DESCRIPTION 
LCD Display
Range  0 - 5.0 seconds (Default 0.2s) 
Description  DC Injection Time. This parameter determines how long the DC is applied when FUN 06 - DC inject 
cong is set to DC at stop, DC on Start or DC at Both.
LCD Display
Range  0 - 100.0% (Default 50.0%) 
Description  DC Injection Level. This parameter congures the amount of DC current to be injected into the motor
  windings. The amount of current is expressed as a percentage of nominal motor current.
Curr Limit Sel  FUN 10 
FUN:  Curr     Lim     Sel 
10              Fixed     Lvls  
LCD Display
Description  Current Limit Select. The S4 drive provides a Current Limit feature. With this feature enabled, the drive’s 
  frequency is automatically reduced when operating in motoring mode to keep the measured current within 
  limits. When operating in regenerative mode, the output frequency will be automatically increased for the 
  same reason.
Parameter Value   Description 
Fixed Lvls (Default)
 The xed levels set in FUN 11 – FUN 14 determine the current limits.
Vin2 
 Vin2 analog input sets the current limit value, range 0–200%. 
Cin 
 Cin analog input sets the current limit value, range 0–200%. 
Vin2 Motor 
 Vin2 analog input sets the motoring current limit value, range 0–200%. 
Cin Motor 
 Cin analog input sets the motoring current limit value, range 0–200%. 
Vin2 F-Mtr 
 Vin2 analog inputs sets the FWD motoring current limit value, range 0–200%. 
Cin F-Motor 
 Cin analog input sets the FWD motoring current limit value, range 0–200%. 
Range