User manual
33
INPUT LINE REQUIREMENTS  
4 - CONNECTIONS 
4.2  Input Line Requirements 
4.2.1  Line Voltage 
See the Power and Current Ratings tables on page 10 for the allowable uctuation of AC line voltage for 
your particular RSi S4 model. A supply voltage above or below the limits given in the table will cause the 
drive to trip with either an overvoltage or undervoltage fault. 
Exercise caution when applying the RSi S4 AC drive on low-line conditions. 
For example, an RSi S4 Series VFD will operate properly on a 208VAC line - but the maximum output 
voltage will be limited to 208VAC. Now if a motor rated for 230VAC line voltage is controlled by this 
drive, higher motor currents and increased heating will result. 
Therefore, ensure that the voltage rating of the motor matches the applied line voltage. If other than 60Hz 
output is desired, proper V/Hz can be programmed into the RSi S4 drive by setting FUN 01 (Nom Mtr 
Volt) and AFN 01 (Nom Mtr Freq) parameters. 
4.2.2  Line Capacity 
If the source of AC power to the RSi S4 drive is greater than 10 times the transformer kVA rating listed in 
the table below, an isolation transformer or line reactor is recommended. Consult the factory for assistance 
in sizing the reactor. 
Recommended Isolation Transformer Sizing for RSi S4 Sensorless Drive
z NOTE: RSi S4 Drives are suitable for use on a circuit capable of delivering not more than 65,000 rms
   symmetrical Amperes at maximum rated Voltage. 
4.2.3  Use of Isolation Transformers and Line Reactors 
In nearly all cases, the RSi S4 drive may be connected directly to a power source. However, in the 
following cases, a properly-sized isolation transformer or line reactor should be utilized to minimize the 
risk of drive malfunction or damage: 
When the line capacity exceeds the ratings of the drive (•  see Section 4.2.2). 
When power factor correction capacitors are used on the drive’s power source. • 
When the power source experiences transient power interruptions or voltage spikes. • 
When the power source supplying the drive also supplies large devices (such as DC drives) that contain • 
controlled rectiers. 
When the drive is powered from an ungrounded (oating) Delta connected source. In this case a drive  • 
isolation transformer utilizing a grounded secondary should be used. 
4.2.4  Phase Imbalance 
Phase voltage imbalance of the input AC source can cause unbalanced currents and excessive heat in the 
drive’s input rectier diodes and DC bus capacitors. Phase imbalance can also damage motors running 
directly across the line. The phase imbalance should not exceed 2% of the voltage rating. 
Drive HP  1   2   3   5   7.5   10   15  20   25 
Transformer kVA  2   4   5   9   13   18   23  28   36 
Drive HP  30   40   50   60   75   100   125   150   200 
Transformer kVA  42   57   70   90   112   150   180   220   250 










