User manual
163
C - S4 PARAMETERS 
11.3  APPENDIX C:  S4 Parameter Groups 
11.3.1 DRV Group
Code  Parameter 
Name 
Default   Range (Options)   Modbus  View 
Only 
Page  User Setting
DRV 01   Nom Mtr Amps   Nominal for Drive  Model Dependant  40001 
75 
DRV 02   Accel Time 1   5.0 sec  0.1 - 3200.0 sec  40002 
76 
DRV 03   Decel Time 1   5.0 sec  0.1 - 3200.0 sec  40003 
76 
DRV 04   Drive Mode 1   0 = Keypad 0 = Keypad
1 = Terminal 1
2 = Terminal 2
3 = Serial
40004 
77 
DRV 05   Freq Mode 1   0 = Keypad 0 = Keypad
1 = Vin1
2 = Cin”
3 = Vin2”
4 = Vin1 6FS”
5 = Vin1 48FS”
6 = Vin1+Cin”
7 = Vin1+Vin2”
8 = Vin1-Cin”
9 = Vin1-Vin2”
10 = Vin1+k*Cin”
11 = Vin1+k*Vin2”
12 = Max Input”
13 = EMOP”
14 = Serial
40005 
78 
DRV 06   Drive Mode 2   2 = Terminal 2 0 = Keypad
1 = Terminal 1
2 = Terminal 2
3 = Serial” 
40006 
78 
DRV 07   Freq Mode 2   1 = Vin1 0 = Keypad
1 = Vin1
2 = Cin
3 = Vin2
4 = Vin1 6FS
5 = Vin1 48FS
6 = Vin1+Cin
7 = Vin1+Vin2
8 = Vin1-Cin
9 = Vin1-Vin2
10 = Vin1+k*Cin
11 = Vin1+k*Vin2
12 = Max Input
13 = EMOP
14 = Serial 
40007 
79 
DRV 08   Output Curr.   Read-Only  0.0 to 999.9 A  40008  X  79 
DRV 09   Output Volts   Read-Only  0 to 1000 V  40009  X  79 
DRV 10   Output Power   Read-Only  0.0 to 655.35 kW  40010  X  79 
DRV 11   MWh Meter   Read-Only  0 to 32767 MWh  40011  X  79 
DRV 12   kWh Meter   Read-Only  0.0 to 999.9 kWh  40012  X  80 
DRV 13   Run Time   Read-Only  0.0 to 6553.5 h  40013  X  80 
DRV 14   Power Time   Read-Only  0 to 65535 h  40014  X  80 
DRV 15   Output Freq   Read-Only  0.0-400.0 Hz  40015  X  80 
DRV 16   Drive Load   Read-Only  -250.0 to 250.0 %  40016  X  80 
DRV 17   Drive Temp   Read-Only  -20.0 to 125.0 
Celcius 
40017  X  81 
DRV 18   Bus Voltage   Read-Only  0 to 1000 Vdc  40018  X  81 