8 - TROUBLESHOOTING & MAINTENANCE 
20   Motor TOL 
Motor timed overload  
trip 
0 
The drive detected an overload 
that exceeds the customer’s 
dened overload setting 
- Check load current demand 
- Verify Motor FLA is
 programmed to the correct value 
- Verify TOL characteristic is 
 correct for the application 
21   Low Temp   Low temperature  0 
This fault occurs if the 
temperature of the heatsink falls 
below -10.0 degrees C 
- Verify that ambient temperature  
is within the drive’s specs 
- Increase the ambient 
temperature if necessary 
22   Ref Loss   Speed reference loss  0 
The drive detected the analog 
input was congured to fault if 
the input current went below 
3.0mA
- Check physical connections for 
reference signal 
- Check that programming for 
4-20 mA signal is correct 
- Verify signal to drive is correct, 
see AFN 29
23   Brk Wire 
Broken wire 
detection 
0 
The drive detected that the 
potentiometer circuit wiring 
opened and generated a fault 
- Check wiring for loss of 
connection to control terminals 
- Check that a proper-value 
potentiometer is installed 
24   Keypad Loss   Keypad loss 
0 
This fault occurs because of a 
problem with the keypad or a 
keypad connection. It occurs if 
the drive detects that it cannot 
read any key presses 
- Check the connection from 
keypad to control board. Note 
that they keypad is not designed 
for remote mounting 
1 
This fault occurs because of a 
problem with the keypad, a 
keypad connection, or the wrong 
keypad is being used. It occurs if  
the keypad ID for an S4 cannot 
be read 
2 
This fault occurs because of a 
problem with the keypad or a 
keypad connection. It occurs if 
the drive detects that it cannot 
write to the LCD 
25   Comm Loss   Communication loss  0 
This fault occurs when the drive 
is in a serial link control path and  
the amount of time since the last 
Modbus comm. exceeds the time 
set in parameter I/O 49 
- Check connections to the 
Modbus port. Adjust value of 
parameter I/O 49 as needed 
26   Regen Time   Regen timeout  0 
This fault occurs if the drive 
takes more time to decelerate to a  
stop than is allowed. The 
timeout is determined by the 
longest deceleration ramp time 
(Decel 1 or Decel 2) plus the 
Regen Timeout parameter 
- Reduce the amount of 
regenerative energy or increase 
the Regen timeout parameter, 
FUN 18
27   Pwr Bridge   Power bridge fault  0, 1, 2 
The drive detected a failure in the  
output power devices 
- Check for failed input power 
device 
28   Drive TOL   Drive timed overload  0 
The drive sensed an overload that  
exceeded the drive rating 
- Consult factory 
29   Stuck Key   Stuck key error  0 
This fault occurs if a key press is 
detected upon power-up. This 
would occur because of a 
defective keypad or because 
someone was holding down a key  
when powering-up the drive 
- Check for stuck keypad and 
repair or replace 
- Consult factory 