7 - PARAMETER DESCRIPTION
Bits 4, 5, 6
of Seq Cntl
Description of Seq Count Function (Bits 4, 5, 6)
000
Time Base - The current sequencer state will last for a time interval equal to the number “Seq
Count X” multiplied by the time base congured in the Seq Appl (APP 01) parameter.
Seq Appl Setting
Time to
Advance
Max Seq Time
1 sec Base (1 sec) * (Seq Cnt X)
18.2 hours
0.1 sec Base (0.1 sec) * (Seq Cnt X)
1.82 hours
0.01 sec Base (0.01 sec) * (Seq Cnt X)
10.92 minutes
001
Pulse Count - The current sequencer state will last until the number of pulses programmed into “Seq
Count X” is detected on terminal Vin1.
010
Low Analog Voltage Threshold - The active sequencer state lasts until the voltage signal applied to
terminal Vin2 is < a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
011
High Analog Voltage Threshold - The active sequencer state lasts until the voltage signal applied to
terminal Vin2 is > a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
100
Low Analog Current Threshold - The active sequencer state lasts until the current signal applied to
Cin terminals is < a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
101
High Analog Current Threshold - The active sequencer state lasts until the current signal applied to
Cin Terminals is > a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
110
Digital Comparison - The active sequencer state lasts until the binary value of digital inputs
congured to Seq1, Seq2 and Seq3 is equal to the value programmed into “Seq Count X”.
NOTE: “DIx Congure” parameters must be set to “Seq1, Seq2, and Seq3”.
Digital Input Terminals
Description
Seq 1 Seq 2 Seq 2
0 0 0
No Input active
1 0 0
Seq 1 active
0 1 0
Seq 2 active
1 1 0
Seq 1 & Seq 2 active
0 0 1
Seq 3 active
1 0 1
Seq 1 & Seq 3 active
0 1 1
Seq 2 & Seq 3 active
1 1 1
Seq 1, Seq 2, Seq 3 active
111
The sequencer will never advance if this option is selected