User manual

128
Wake-Up Dly AFN 43
PID Ref AFN 44
PID FB AFN 45
AFN: Wake-Up Dly
43 0.0sec
AFN: PID Ref
44 0.00%
AFN: PID FB
45 0.00%
7 - PARAMETER DESCRIPTION
LCD Display
Range 0.00 to 300.0 seconds (Default 0.0s)
Description This parameter sets the wake-up delay time. When the PID signal (AFN 39 selection) becomes greater
than the Wake Up Level (AFN 41), the drive waits for this Wake-Up Delay time to expire before resuming
output.
See also AFN 39 - PID Sleep
LCD Display
Range 0.00 to 100.00% (view only)
Description This parameter shows the set point for the PID control loop. The set point is expressed as a percentage of
the maximum frequency. The value shown in this parameter can be used to determine whether the control
path of the drive is congured correctly.
LCD Display
Range 0.00 to 100.00% (view only)
Description This parameter shows the feedback signal as a percentage of the maximum frequency. This parameter
may be used to determine if the analog input is congured correctly with respect to span and offset. It can
also be sent to either the Imet or Vmet analog output terminal if the analog output is congured to the PID
feedback signal.
PID Error AFN 46
AFN: PID Error
46 +0.00%
LCD Display
Range 0.00 to 100.00% (view only)
Description This parameter shows the value of the error between AFN 45 - PID FB and AFN 44 - PID Ref.