User manual
113
Carrier Freq  AFN 05 
Slip Comp  AFN 06 
AFN: Carrier Freq
05   3.0kHz  
AFN: Slip     Comp 
06 No 
7 - PARAMETER DESCRIPTION 
LCD Display
Range  0.6 to 16.0 kHz (Default 3.0 kHz) 
Description  This parameter congures the switching (or carrier) frequency for the drive. Lower frequencies produce 
  better torque, but produce more audible noise from the motor. Higher switching frequencies produce less 
  audible noise, but cause more heating in the drive and motor. 
 z NOTE: This parameter is not adjustable during Run mode. 
See also  page 34 for information on motor lead lengths.
 High carrier frequencies and long lead lengths can lead to premature motor and/or drive failure.  
LCD Display
Range
Parameter Value Description
No (Default)
Slip compensation is not utilized 
Yes 
The drive calculates how much slip compensation is needed depending on the load and motor speed 
Description  This parameter sets the amounts of slip compensation which may help maintain constant motor speed 
  under changing load conditions.
V-BoostConf AFN07
AFN: V-Boost     Conf 
07                                1.0%  
LCD Display
Range  0.00 to 50% (Default 1.0%) 
Description  This parameter sets the amount of boost (expressed as a percentage of nominal motor voltage) to be applied 
at zero frequency. The amount congured then tapers linearly as frequency increases, reaching zero at the 
point specied by parameters AFN 08 - Bst Tpr Frq and AFN 09 - Bst Tpr Vlt. 
  This parameter is used when FUN 02 - Torque Curve is set to Linear Fxd, Linear Auto, Pump Fxd, or Fan 
Fxd.
  z NOTE: This parameter is not used when the drive is in Vector mode.