User manual

105
7 - PARAMETER DESCRIPTION
Vin2 Filter I/O 30
I/O: Vin2 Filter
30 15ms
LCD Display
Range 1 to 100ms (Default 15ms)
Description This parameter sets the low-pass lter time for the analog input signal being received at terminals Vin2.
Longer lter times better reduce noise disturbances but will also slow the signal response time.
See also I/O 27, 28, 29, 31
Set K-factor I/O 31
I/O: Set k-Factor
31 0.0%
LCD Display
Range 0 to 100% (Default 0.0%)
Description When parameters DRV 05 (Freq Mode 1) or DRV 07 (Freq Mode 2) are set to “Vin1 + k * Vin2”, this
parameter sets the value of k, which is the scale factor by which reference 2 is multiplied before being
added to reference 1.
See also I/O 27, 28, 29, 30
Vmet – Imet I/O 32, 33
I/O: Vmet Cong
32 Out Freq
I/O: Imet Cong
33 Out Torque
LCD Display
Parameter Value Function
Not Assign
Output is not used
Out Freq (I/O 32 Default)
Percentage of nominal motor frequency supplied to the motor. (see AFN01)
Out Torque (I/O 33 Default)
Estimated percentage of torque
Out Volt
Percentage of full voltage supplied to the motor (see FUN01)
Out Power
Percentage of calculated power (max is 250% of drive rating)
Ref Freq
Percentage of maximum frequency commanded (see AFN04)
PID Fback
Percentage of full scaled PID output (0-100%)
Bus Voltage
Percentage of nominal DC bus level
Output Curr
Percentage of output current
Range
Description Analog voltage output and Analog current output congure. These parameters congure what variable
governs the analog outputs Vmet and Imet. Vmet is a 0 to 10VDC output, Imet is a 0 to 20mA output.
See also I/O 34, 35, 36, 40, 41