User manual

102
Vin1Offset I/O21
Vin1 Filter I/O 22
I/O: Vin1 Oset
21 0.0%
I/O: Vin1 Filter
22 15ms
7 - PARAMETER DESCRIPTION
LCD Display
Range 0.0 to 100% (Default 0.0%)
Description This parameter is used to alter the starting value of the input being received at Vin1 terminals (analog).
For example, with a 0 to 10VDC input, setting this parameter to a value of 10% alters the range to
1 to 10VDC.
LCD Display
Range 1 - 1000 ms (Default 15ms)
Description This parameter sets the low-pass lter time for the analog input signal being received at Vin1 terminals
(analog). Longer lter times better reduce noise disturbances but will also slow the signal response time.
CinCong I/O23
I/O: Cin Cong
23 0 - 20mA 50
LCD Display
Range
Description Cin Cong selects the type of signal for analog input Cin. Parameters I/O 25 (Cin Offset) and I/O 24 (Cin
Span) may be used to customize the selected range.
z NOTE: When the signal range is inverted the minimum input corresponds to the maximum output,
while the maximum input corresponds to the minimum output.
See also DRV 05 on page 78.
“Description of Control Terminals” on page 41
Parameter Value Function
4-20mA 50 4 to 20 mA current signal with 50 Ohm load
4-20mA 50I 4 to 20 mA current signal with 50 Ohm load inverted
0-20mA 50 +++ 0 to 20 mA current signal with 50 Ohm load
0-20mA 50I 0 to 20 mA current signal with 50 Ohm load inverted