7 - PARAMETER DESCRIPTION
Jump Code I/O 00
I/O: Jump Code
00 25
7.1.3 I/O Group
LCD Display
Description By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter
within the group.
Active Logic I/O 01
I/O: Active Logic
01 Active High
LCD Display
Range
The digital inputs must be within the specied voltages or unintended operation may result,
causing machinery and/or personal damage.
Parameter Value Description
Active Low
Low input is true (“pull-down logic”); all digital inputs are referenced to Dcom.
Active High (Default)
High input is true (“pull-up logic”); all digital inputs are referenced to +24.
Description This parameter determines whether a high or a low input is regarded as active. A “high input” is input
voltage between 10 and 24 VDC; a “low input” is voltage between 0 and 3 VDC. Any value in between is
considered unspecied and is not supported.
Note that the EN (Enable) terminal on the TB4 terminal group is not affected by the setting of this
parameter. A high input to the EN terminal is always regarded as active. Thus, if the input to the terminal
goes low, the drive will not operate, even if pull-down logic is congured.