7 - PARAMETER DESCRIPTION
Jump Code I/O 00
I/O: Jump Code
00 25
7.1.3 I/O Group
LCD Display
Description By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter
within the group.
Active Logic I/O 01
I/O: Active Logic
01 Active High
LCD Display
Range
The digital inputs must be within the specied voltages or unintended operation may result,
causing machinery and/or personal damage.
Parameter Value Description
Active Low
Low input is true (“pull-down logic”); all digital inputs are referenced to Dcom.
Active High (Default)
High input is true (“pull-up logic”); all digital inputs are referenced to +24.
Description This parameter determines whether a high or a low input is regarded as active. A “high input” is input
voltage between 10 and 24 VDC; a “low input” is voltage between 0 and 3 VDC. Any value in between is
considered unspecied and is not supported.
Note that the EN (Enable) terminal on the TB4 terminal group is not affected by the setting of this
parameter. A high input to the EN terminal is always regarded as active. Thus, if the input to the terminal
goes low, the drive will not operate, even if pull-down logic is congured.