Technical information

5 – PARAMETER DESCRIPTIONS
84
P69 Meter FUN 01, FUN02
LCD Display
FUN: Meter 1
01 Ave Current
FUN: Meter 2
02 Ave Volts
Range 0 – 25 (Default 1 for meter 1, 7 for meter 2)
Description For the LED display, parameter P69 configures which single meter is displayed on the main screen.
For the LCD display, parameters FUN 01and FUN 02 configure which meters are displayed on the
two lines of the main display screen.
Options LED LCD
0 Status Running State (LED meter only)
1 Ave Current Average current (Default meter 1)
2 L1 Current Current in phase 1
3 L2 Current Current in phase 2
4 L3 Current Current in phase 3
5 Cur Imbal Current Imbalance %
6 Ground Fault Residual Ground Fault % FLA
7 Ave Volts Average Voltage L-L RMS (Default meter 2)
8 L1-L2 Volts Voltage in, L1 to L2 RMS
9 L2-L3 Volts Voltage in, L2 to L3 RMS
10 L3-L1 Volts Voltage in, L3 to L1 RMS
11 Overload Thermal overload in %
12 Power Factor Motor power factor
13 Watts Motor real power consumed
14 VA Motor apparent power consumed
15 VARS Motor reactive power consumer
16 kW hours Kilo-watt-hour used by the motor, wraps at 1,000
17 MW hours Mega-watt-hour used by the motor, wraps at 10,000
18 Phase Order Phase Rotation
19 Line Freq Line Frequency
20 Analog Input Analog Input %
21 Analog Output Analog Output %
22 Run Days Running time in days, wraps at 2,730 days
23 Run Hours Running time in Hours and Minutes, wraps at 24:00
24 Starts Number of Starts, wraps at 65,536
25 TruTorque % TruTorque %
26 Power % Power %
P70 Starter Model Number FUN 13
LCD Display
FUN: Starter MN
13 None
Description The Starter Model Number parameter configures the thermal protection of the starter power stack.
This information is useful for future service reasons. If calling Benshaw for service, this number
should be recorded so it can be provided to the service technician.