Technical information

5 – PARAMETER DESCRIPTIONS
81
P64 Starter Type FUN 07
LCD Display
FUN:Starter Type
07 Normal
Range nor,Id,y-d, PctL, cFol, AtL (Default nor)
Description The MX has been designed to be the controller for many control applications; Solid State Starter,
both Normal (outside Delta) and Inside Delta, and electromechanical starters, Wye Delta, Across the
line full voltage starter, Phase Control/Voltage Follower, Current Follower. In each case, the MX is
providing the motor protection and the necessary control for these applications.
Options LED LCD
nor Normal Normal (Outside Delta), Reduced Voltage Soft Starter RVSS (Default)
Id Inside Delta Inside Delta, RVSS
y-d Wye-Delta Wye Delta
PctL Phase Control Open Loop Phase control / voltage follower using external input
reference.
cFol Current Follow Closed Loop Current follower using external input reference.
AtL ATL Across the line (Full Voltage)
NOTE: For single phase operation, select Normal for the Starter Type parameter, and Single Phase
for the phase order parameter
See Also Phase Order parameter on page 83
Application section 6.2, Other Applications using the MX, on page 91
Theory of Operation section 8.5, Wye-Delta Operation, on page 129
Theory of Operation section 8.6, Phase Control, on page 131
Theory of Operation section 8.7, Current Follower, on page 133
Theory of Operation section 8.8, Across The Line / Full Voltage Operation, on page 134