Technical information

5 – PARAMETER DESCRIPTIONS
79
P60 Communication Baud Rate FUN 11
LCD Display
FUN:Com Baudrate
11 9600
Range 1.2, 2.4, 4.8, 9.6, 19.2 Kbps (Default 9.6)
Description The Communication Baud Rate parameter sets the baud rate for Modbus communications.
See Also Local Source parameter on page 43
Remote Source parameter on page 44
Communication Drop Number parameter on page 79
Communication Timeout parameter on page 78
P61 Communication Drop Number FUN 10
LCD Display
FUN: Com Drop #
10 1
Range 1 – 247 (Default 1)
Description The Communication Drop Number parameter sets the starter’s address for Modbus communications.
See Also Local Source parameter on page 43
Remote Source parameter on page 44
Communication Baud Rate parameter on page 79
Communication Timeout parameter on page 78
P62 Energy Saver FUN 09
LCD Display
FUN:Energy Saver
09 Off
Range On – Off (Default OFF)
Description The energy saver feature lowers the voltage applied to a lightly loaded motor. It continues to lower
the voltage until it finds the point where the current reaches its lowest stable level and then regulates
the voltage around this point. If the load on the motor increases, the starter immediately returns the
output of the starter to full voltage.
NOTE: This function does not operate if a bypass contactor is used once the motor is up to speed.
NOTE: In general, Energy Saver can save approximately 1000 watts per 100 HP. Consult Benshaw
for further detail.