P58 Miscellaneous Commands FUN 15
LCD Display
FUN:Misc Command
15 None
Range 0 – 6 (Default 0)
Description The Miscellaneous Commands parameter is used to issue various commands to the MX starter.
The Reset Run Time command resets the user run time meters back to zero (0).
The Reset kWh command resetsthe accumulated kilowatt-hour and megawatt-hour meters back to
zero (0).
The Reflash Mode command puts the MX into a reflash program memory mode. The reflash mode
can only be entered if the MX starter is idle. When the reflash mode is entered, the MX waits to be
programmed. The onboard LED display shows “FLSH”. The remote display is disabled after
entering reflash mode. The MX does not operate normally until reflash mode is exited. Reflash
mode may be exited by cycling control power.
The Store command allows the user to copy the parameters into non-volatile memory as a backup. If
changes are being made, store the old set of parameters before any changes are made. If the new
settings do not work, the old parameter values can be loaded back into memory.
The Load command loads the stored parameters into active memory.
The Factory Reset command restores all parameters to the factory defaults. These can be found
section 4.
Options LED LCD
0 None No commands
1 Reset Run Time Reset Run Time Meter
2 Reset kWh/MWh Reset kWh/MWh Meters
3 Reflash Mode Activate Reflash Mode
4 Store Parm The current parameter values are stored in non-volatile memory
5 Load Parm All parameter are retrieved from non-volatile memory
6 Factory Rst All parameters are restored to the factory defaults
P59 Communication Timeout FUN 12
LCD Display
FUN:Com Timeout
12 Off
Range OFF, 1 – 120 seconds (Default OFF)
Description The Communication Timeout parameter sets the time that the starter continues to run without
receiving a valid Modbus request. If a valid Modbus request is not received for the time that is set,
the starter declares an F82 (Modbus Time Out). The starter performs a controlled stop.
See Also Stop Mode parameter on page 53
Local Source parameter on page 43
Remote Source parameter on page 44
Controlled Fault Stop Enable parameter on page 64
Communication Drop Number parameter on page 79
Communication Baud Rate parameter on page 79