Technical information
Table Of Contents

5 – PARAMETER DESCRIPTIONS
77
P55 Keypad Stop Disable I/O 17
LCD Display
I/O:Kpd Stop Dis
17 Enabled
Range Enabled – Disabled (Default Enabled)
Description If “Disabled”
When this parameter is set to Disabled, the keypad Stop button is de-activated. This should be done
with caution, as the STOP will not stop the starter.
If the keypad is selected as local or remote control sources, the “STOP” key cannot be disabled.
If “Enabled”
When this parameter is set to Enabled, the keypad stop button is enabled and stops the starter
regardles off the selected control source (keypad, terminal or serial).
Option LED LCD
Off Disabled Keypad Stop does not stop the starter
On Enabled Keypad Stop does stop the starter (Default Enabled)
See Also Local Source parameter on page 43
Remote Source parameter on page 44