Technical information

5 – PARAMETER DESCRIPTIONS
70
P42, P43, P44 Relay Output Configuration I/O 04, I/O 5, I/O 06
LCD Display
I/O: R1 Config
04 Fault FS
I/O: R2 Config
05 Running
I/O: R3 Config
06 UTS
Description I/O parameters 1 – 3 configure which functions are performed by the R1 to R3 relays
Options LED LCD
OFF Off OFF, Not Assigned, Output has no function or may be controlled over
Modbus
FLFS Fault FS Faulted – Fail Safe operation, energized when no faults present, de-
energized when faulted (Default R1)
FLnF Fault NFS Faulted– Non Fail Safe operation, de-energized when no faults present,
energized when faulted
run Running Running, starter running, voltage applied to motor (Default R2)
utS UTS Up to Speed, motor up to speed (Default R3) or transition to for
Wye/Delta Operation
AL Alarm Alarm, any alarm condition present
rdyr Ready Ready, starter ready for start command
LOC Locked Out Locked Out
OC Over Current Over Current Alarm, over current condition detected.
UC Under Current Under Current Alarm, under current condition detected.
OLA OL Alarm Overload Alarm
ShFS Shunt FS Shunt Trip Relay – Fail Safe operation, energized when no shunt trip
fault present, de-energized on shunt trip fault.
ShnF Shunt NFS Shunt Trip Relay – Non Fail Safe operation, de-energized when no
shunt trip fault present, energized on shunt trip fault
GfLt Ground Fault A Ground Fault trip has occurred.
ES Energy Saver Operating in Energy Saver Mode.
HEAt Heating Motor Heating, starter applying heating pulses to motor.