Technical information
Table Of Contents

5 – PARAMETER DESCRIPTIONS
69
P39, P40, P41 Digital Input Configuration I/O 01, I/O 02, I/O 03
LCD Display
I/O:DI 1 Config
01 Stop
I/O:DI 2 Config
02 Bypass Cnfrm
I/O:DI 3 Config
03 Fault Low
Description I/O parameters 1 – 3 configure which functions are performed by the D1 to D3 terminals.
Options LED LCD
OFF OFF OFF, Not Assigned, Input has no function
StOP Stop Command a Stop to remove the software seal in for 3-wire control
(Default DI 1)
FH Fault High Fault High, Fault when input is asserted, 120V applied.
FL Fault Low Fault Low, Fault when input is de-asserted, 0V applied (Default DI 3)
Fr Fault Reset Fault Reset, Reset when input asserted, 120V applied.
byP Bypass Cnfrm Bypass/2M, bypass contactor feedback, 2M contactor feedback in full
voltage or Wye-delta (Default DI 2)
EoLr EOL Reset Emergency Motor Overload content reset. After an OL trip has
occurred Reset when input asserted, 120V applied.
L-r Local/remote Local/Remote control source, Selects whether the Local Source
parameter or the Remote Source parameter is the control source. Local
Source is selected when input is de-asserted, 0V applied. Remote
Source selected when input asserted, 120V applied.
hdIS Heat Disable Heat Disable, Heater disabled when input asserted, 120V applied.
hEn Heat Enabled Heat Enabled, Heater enabled when input asserted, 120V applied.
rSEL Ramp Select Ramp 2 selection, Ramp 2 is enabled when input asserted, 120V
applied.
See Also Bypass Feedback Time parameter on page 76
Local Source parameter on page 43
Remote Source parameter on page 44
Heater Level parameter on page 80
Application section 6.2.1, Wye Delta, on page 91
Theory of Operation section 8.1.10, Emergency Motor Overload Reset, on page 116
Theory of Operation section 8.5, Wye-Delta Operation, on page 129
Theory of Operation section 8.3.6, Dual Acceleration Ramp Control, on page 125
Theory of Operation section 8.9, Start/Stop Control with a Hand/Off/Auto Selector Switch, on page
135