5 – PARAMETER DESCRIPTIONS
59
P25 Over Current Time PFN 02
LCD Display
PFN:Over Cur Tim
02 0.1 sec
Range Off, 0.1 – 90.0 seconds (Default 0.1 sec)
Description The Over Current Time parameter sets the period of time that the motor current must be greater than
the Over Current Level parameter before an over current fault and trip occurs.
If OFF is selected, the over current timer does not operate and the starter does not trip. It energizes
any relay set to Overcurrent until the current drops or the starter trips on an overload.
A shear pin function can be implemented by setting the delay to its minimum value.
See Also Over Current Level parameter on page 58
Relay Output Configuration parameters on page 70
Auto Reset parameter on page 64
Controlled Fault Stop Enable parameter on page 64