P23 Kick Time 2 CFN 13
LCD Display
CFN: Kick Time 2
13 1.0 sec
Range 0.1 – 10.0 seconds (Default 1.0 sec)
Description The Kick Time 2 parameter sets the length of time that the kick current level is applied to the motor
when the second ramp is active. Refer to the Kick Time 1 parameter for description of operation.
See Also Kick Time 1 parameter on page 52
Digital Input Configuration parameters on page 69
Theory of Operation section 8.3.2, Programming A Kick Current, on page 119
Theory of Operation section 8.3.6, Dual Acceleration Ramp Control, on page 125
P24 Over Current Level PFN 01
LCD Display
PFN:Over Cur Lvl
01 Off
Range OFF, 50 – 800 % of FLA (Default OFF)
Description If the starter detects a one cycle, average RMS current that is greater than the level defined, an over
current alarm condition exists and the alarm relay energizes if defined. The over current timer starts
a delay time. If the over current still exists when the delay timer expires, the starter Over Current
Trips (F31) and the fault relay de-energizes.
The Over Current Trip is only active in the UTS state, Energy Saver state, Current follower or while
in the Phase Control mode.
A relay can be programmed to change state when an over current alarm condition is detected.
See Also Over Current Time parameter on page 59
Relay Output Configuration parameters on page 70
Auto Reset parameter on page 64
Controlled Fault Stop Enable parameter on page 64
Time
Alarm
Condition
Fault
Trip
% Current
Delay
PFN 02/P25
Over Cur Lvl
PFN 01/P24
Motor FLA
QST 01/P1