Technical information

5 – PARAMETER DESCRIPTIONS
57
P20 Maximum Current 2 CFN 07
LCD Display
CFN: Max Cur 2
07 600 %
Range 100 – 800 % of FLA (Default 600%)
Description The Maximum Current 2 parameter is set as a percentage of the motor FLA parameter setting, when
the second ramp is active. Refer to the Maximum Current 1 for description of operation.
See Also Maximum Current 1 parameter on page 46
Digital Input Configuration parameters on page 69
Theory of Operation section 8.3.1, Current Ramp Settings, Ramps and Times, on page 118
Theory of Operation section 8.3.6, Dual Acceleration Ramp Control, on page 125
P21 Ramp Time 2 CFN 05
LCD Display
CFN: Ramp Time 2
05 15 sec
Range 0 – 300 seconds (Default 15 seconds)
Description The Ramp Time 2 parameter the time it takes for the starter to allow the current to go from the initial
current to the maximum current when the second ramp is active. Refer to the Ramp Time 1
parameter for description of operation.
See Also Ramp Time 1 parameter on page 47
Digital Input Configuration parameters on page 69
Theory of Operation section 8.3.1, Current Ramp Settings, Ramps and Times, on page 118
Theory of Operation section 8.3.6, Dual Acceleration Ramp Control, on page 125
P22 Kick Level 2 CFN 12
LCD Display
CFN: Kick Lvl 2
12 Off
Range OFF, 100 – 800% of FLA (Default OFF)
Description The Kick Level 2 parameter sets the current level that precedes any ramp when a start is first
commanded when the second ramp is active. Refer to the Kick Level 1 parameter for description of
operation.
See Also Kick Level 1 parameter on page 52
Digital Input Configuration parameters on page 69
Theory of Operation section 8.3.2, Programming A Kick Current, on page 119
Theory of Operation section 8.3.6, Dual Acceleration Ramp Control, on page 125