P7 Maximum Current 1 QST 07, CFN 04
LCD Display
QST: Max Cur 1
07 600 %
CFN: Max Cur 1
04 600 %
Range 100 – 800 % of FLA (Default 600%)
Description The Maximum Current 1 parameter is set as a percentage of the motor FLA parameter setting. The
Maximum Current 1 parameter performs two functions. It sets the current level for the end of the
ramp profile. It also sets the maximum current that is allowed to reach the motor after the ramp is
completed.
If the ramp time expires before the motor has reached full speed, the starter holds the current at the
maximum current level until the UTS timer expires, the motor reaches full speed, or the overload
trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of
a lower maximum current.
See Also Initial Current 1 parameter on page 45
Ramp Time 1 parameter on page 47
Up To Speed Time parameter on page 48
Kick Level 1 parameter on page 52
Kick Time 1 parameter on page 52
Start Mode parameter on page 49
Theory of Operation section 8.3.1, Current Ramp Settings, Ramps and Times, on page 118