Technical information

4 – PARAMETERS
36
4.4.5 Function Group
Group Display Description Setting Range Units Default Page
FUN 00 Jump Code Jump to parameter 1 – 16 1
FUN 01 Meter 1 Meter 1 Ave
Current
FUN 02 Meter 2 Meter 2
Ave Current
L1 Current
L2 Current
L3 Current
Curr Imbal
Ground Fault
Ave Volts
L1-L2 Volts
L2-L3 Volts
L3-L1 Volts
Overload
Power Factor
Watts
VA
VARS
kW hours
MW hours
Phase Order
Line Freq
Analog Input
Analog Output
Run Days
Run Hours
Starts
TruTorque %
Power %
Ave
Volts
84
FUN 03 CT Ratio CT Ratio 72, 96, 144, 288, 864,
1320, 2640, 2880, 3900,
5760, 8000, 14400, 28800
288 83
FUN 04 Phase Order Phase Order Insensitive
ABC
CBA
Single Phase
Insens. 83
FUN 05 Rated Volts Rated Voltage 100, 110, 120, 200, 208,
220, 230, 240, 350, 380,
400, 415, 440, 460, 480,
500, 525, 575, 600, 660,
690, 1000, 1140, 2200,
2300, 2400, 3300, 4160,
4600, 4800, 6000, 6600,
6900, 10000, 11000,
11500, 12000, 12470,
13200, 13800
RMS
Voltage
480 82
FUN 06 Motor PF Rated Power Factor -0.01 (Lag) – 1.00 (Unity) -0.92 82
FUN 07 Starter Type Starter Type Normal
Inside Delta
Wye-Delta
Phase Ctl
Curr Follow
ATL
Normal 81
FUN 08 Heater Level Heater Level Off, 1 25 %FLA Off 80
FUN 09 Energy Saver Energy Saver Off, On Off 79
FUN 10 Com Drop # Communication Drop Number 1 – 247 1 79
FUN 11 Com Baudrate Communication Baud Rate 1200
2400
4800
9600
19200
bps 9600 79