Technical information

4 – PARAMETERS
35
4.4.4 I/O Group
Group Display Description Setting Range Units Default Page
I/O 00 Jump Code Jump to parameter 1 – 17 1
I/O 01 DI 1 Config DI 1 Configuration Stop
I/O 02 DI 2 Config DI 2 Configuration Bypass
Cnfrm
I/O 03 DI 3 Config DI 3 Configuration
Off
Stop
Fault High
Fault Low
Fault Reset
Bypass Cnfrm
E OL Reset
Local/Remote
Heat Disable
Heat Enable
Ramp Select
Fault
Low
69
I/O 04 R1 Config R1 Configuration Fault FS
I/O 05 R2 Config R2 Configuration Running
I/O 06 R3 Config R3 Configuration
Off
Fault FS (Fail Safe)
Fault NFS (Non Fail Safe)
Running
UTS
Alarm
Ready
Locked Out
Overcurrent
Undercurrent
OL Alarm
Shunt Trip FS
Shunt Trip NFS
Ground Fault
Energy Saver
Heating
UTS
70
I/O 07 Ain Trp Type Analog Input Trip Type Off
Low Level
High Level
Off 71
I/O 08 Ain Trp Lvl Analog Input Trip Level 0 – 100 % 50 72
I/O 09 Ain Trp Tim Analog Input Trip Time 0.1 – 90.0 Seconds 0.1 72
I/O 10 Ain Span Analog Input Span 1 – 100 % 100 73
I/O 11 Ain Offset Analog Input Offset 0 99 % 0 74
I/O 12 Aout Fctn Analog Output Function Off
0 – 200% Curr
0 – 800% Curr
0 – 150% Volt
0 – 150% OL
0 – 10 kW
0 – 100 kW
0 – 1 MW
0 – 10 MW
0 – 100% Ain
0 – 100% Firing
Calibration
Off 74
I/O 13 Aout Span Analog Output Span 1 – 125 % 100 75
I/O 14 Aout Offset Analog Output Offset 0 – 99 % 0 75
I/O 15 Inline Confg Inline Configuration Off, 1.0 10.0 Seconds 3.0 76
I/O 16 Bypas Fbk Tim Bypass Feedback Time 0.1 5.0 Seconds 2.0 76
I/O 17 Kpd Stop Dis Keypad Stop Disable Enabled, Disabled Enabled 77